r_20261029_173926_9afa
done- drawing
- drawing.png
- reference
- transformer-protection-v1
- at
- 2026-10-29T17:39:26Z
Summary
Single points of failure
1 component: if any one of these fails on its own, the supply is lost.
- {
XFMR}
Pairs
2 pairs: the supply is lost only if both components of a pair fail together.
- {
CB5-1,CB5-2} - {
CB7-1,CB7-2}
Click a set to highlight its components on the drawing and in the block diagram; click it again to clear.
Drawing and graph
block (can fail)perfect connectorin a cut-set difference
Hover a box to see its own connections.
Not on the drawing
| node | type | connected to | why |
|---|---|---|---|
SRC-765 | source | B71, B72 | Spec requires source connected to B71 and B72 |
SINK-500 | sink | B51, B52 | Spec requires sink connected to B51 and B52 |
Cut sets
Against the reference: pass
No differences.
This model
Minimal cut sets up to order 3. Click an order to show or hide it.
Order 1 (1)
- {
XFMR}
Order 2 (2)
- {
CB5-1,CB5-2} - {
CB7-1,CB7-2}
Gaps
None flagged.
Assumptions
Can fail: breaker, transformer. Spec: only the four breakers and the transformer can fail; CTs and buses are perfect connectors.
Success: any_path. Spec: any one source-to-sink path is enough.
Not modelled:
- Protection relays, CT secondaries, BFI links, RTD, 34 kV tertiary: Out of scope per spec (primary power path only).
- Bus and CT failures: Treated as perfect connectors per spec.
- Operating errors: None in this study per spec.