Summary

Single points of failure

1 component: if any one of these fails on its own, the supply is lost.

Pairs

2 pairs: the supply is lost only if both components of a pair fail together.

Click a set to highlight its components on the drawing and in the block diagram; click it again to clear.

Drawing and graph

block (can fail)perfect connectorin a cut-set difference

Hover a box to see its own connections.

B71 (busbar), confidence 0.9B71B72 (busbar), confidence 0.9B72CB7-1 (breaker), confidence 0.9CB7-1CB7-2 (breaker), confidence 0.9CB7-2B7T (busbar), confidence 0.8B7TXFMR (transformer), confidence 0.8XFMRB5T (busbar), confidence 0.8B5TCB5-1 (breaker), confidence 0.9CB5-1CB5-2 (breaker), confidence 0.9CB5-2B51 (busbar), confidence 0.9B51B52 (busbar), confidence 0.9B52
Page 1

Not on the drawing

nodetypeconnected towhy
SRC-765sourceB71, B72Spec: source connected to B71 and B72
SINK-500sinkB51, B52Spec: sink connected to B51 and B52

Cut sets

Against the reference: pass

No differences.

This model

Minimal cut sets up to order 3. Click an order to show or hide it.

Order 1 (1)
  • {XFMR}
Order 2 (2)
  • {CB5-1, CB5-2}
  • {CB7-1, CB7-2}

Gaps

None flagged.

Assumptions

Can fail: breaker, transformer. Spec: only the four breakers and the transformer can fail; CTs and buses are perfect connectors.

Success: any_path. Spec: any one source-to-sink path is enough.

Not modelled:

  • Protection relays, CT secondaries, BFI links, RTD, 34 kV tertiary: Out of scope per spec.
  • Operating errors: Spec: none in this study.