If these are right, every cut set is right: the cut sets are computed from the paths and what can fail.
1 · Power reaches the load by these paths
Click a path to light it up on the drawing. Is every part on that route boxed, and nothing extra?
2 · Parts not on the drawing
3 · Assumptions
Opens your email with what you ticked, what you didn't, and your note.
Summary
Single points of failure
5 components: if any one of these fails on its own, the supply is lost.
- {
B7RX} - {
BNRX} - {
CBRX} - {
Neutral Rx} - {
Three Phase Rx}
Pairs
4 pairs: the supply is lost only if both components of a pair fail together.
- {
B71,B72} - {
B71,CB7-2} - {
B72,CB7-1} - {
CB7-1,CB7-2}
Click a set to highlight its components on the drawing and in the block diagram; click it again to clear.
Drawing and graph
Hover a box to see its own connections.
Not on the drawing
| node | type | connected to | why |
|---|---|---|---|
765kV System | source | B71, B72 | Virtual source representing the 765 kV grid behind Bus 1 and Bus 2; drawing shows only the bus stubs. |
Cut sets
Reference: none
No verdict: nothing was compared with a reference. These are the model's own cut sets.
This model
Minimal cut sets up to order 3. Click an order to show or hide it.
Order 1 (5)
- {
B7RX} - {
BNRX} - {
CBRX} - {
Neutral Rx} - {
Three Phase Rx}
Order 2 (4)
- {
B71,B72} - {
B71,CB7-2} - {
B72,CB7-1} - {
CB7-1,CB7-2}
Gaps
Spare Phase Rx / Spare Neutral RxThe drawing shows the spare reactor connected to B7RX and BNRX with no switching device. I can't tell whether it is energised in normal service (which would add redundancy) or only a hand-swapped spare, so I modelled it as not in service.CB7-1 / CB7-2 / Line tapThe drawing doesn't show whether the arrangement is breaker-and-a-half or ring, or what is beyond the line. I assumed both buses are energised and both breakers are normally closed.
Assumptions
Scope: Primary power path that keeps the 765 kV shunt reactor energised: Bus 1/Bus 2, CB7-1/CB7-2, CBRX, B7RX, Three Phase Rx, BNRX, Neutral Rx.. The drawing is a reactor protection SLD, so reactor availability is the natural reliability question.
Boundary: Source = 765 kV system behind Bus 1 and Bus 2. Sink = reactor neutral grounded (reactor in service).. The reactor can be fed from either bus through CB7-1 or CB7-2, and its circuit is only complete through the neutral reactor to ground.
Can fail: breaker, busbar, other. Breakers, buses and the reactors (phase and neutral) are the primary equipment whose failure takes the reactor out. CTs, VTs and relays are protection/metering only and are left out. The line tap node is just a conductor junction, so it is a perfect connector. The source and sink are virtual.
Success: any_path. The reactor is in service if any closed path exists from the 765 kV system through a bus breaker, CBRX, the phase reactor and the neutral reactor to ground.
Not modelled:
- Spare Phase Rx and Spare Neutral Rx: These are spare units. They are swapped in by hand after a failure, so they are not treated as running in parallel.
- Protection relays (87RXA/O, 87RXB/*, 63/71G/71Q/49), CTs and CCVTs: These are secondary systems. Failure-to-trip and spurious-trip modes are outside this connectivity model.
- The outgoing line: The line runs off the page and is not on the path to the reactor.
- Common-cause failures and switching time: Only independent failures in a static any-path model.